Electric part-turn actuator SPR 0.1PA

Type number: | 238 | |
Max. load torque: | 50 | [Nm] |
Operating time: | 10 to 160 | [s/90°] |
Operating angle: | 60° to 360° | |
Ambient temperature: | -25 to +55 | [°C] |
Protection enclosure: | IP 67 | |
Operating position: | any position | |
Weight: | 3,2 to 5,2 | [kg] |
Standard equipment and functions DMS3
- Supply voltage 230 V AC
- Terminal board connection
- Switching off in limit positions
- 2 freely programmable relays RE1, RE2
- Relay READY
- Control by unified signal 0/4 – 20 mA, 4 – 12 mA, 12 – 20 mA,
or 0/2 – 10 V (not for DMS3 in 2P version) - Control voltage for remote control 24 V DC
- Impulse control (inching duty)
- Timing mode / regime of operation
- Safety function ESD (failure reaction)
- Electronic position transmitter 4-20 mA passive (not for DMS3
in 2P version) - Output for failure messages
- Space heater operated by control unit
- Communication interface RS 232
- Programme for parameters setting by PC
- Mechanical connection – flange ISO 5211
- Manual control
Additional equipment
- Supply voltage 220 V AC, 24 V AC
- Mechanical connection ISO 5211 – flange F07, with bracket
- Mechanical stop ends
- Version with stand, lever and pull-rod